Sizing, benches, heater and ventilation for hotel and spa saunas
Request a Sauna Design ConsultationCommercial sauna design is the planning of a sauna that many bathers use every day: a hotel spa, a resort, a day spa, a gym or a residential club. It settles four things before anything is built: how many people sit in it at the busiest hour, the room volume that follows from that, the heater matched to that volume, and the ventilation and electrical supply that heater needs.
A home sauna is used by a family for an hour in the evening. A commercial sauna runs all day, is opened and closed hundreds of times, and is cleaned between sessions. That is why the sauna is never planned on its own: it is one stop in the aquathermal journey, and it only works if the cold plunge and the rest area are a few steps away.
The room looks the same as a home sauna. What changes is how hard it is worked:
None of this is about the timber or the lighting. It is decided in the brief, and it fixes the room size, the heater and the power supply before an interior designer draws anything.
The room is drawn from the benches outwards. We work in this order:
Heat rises and collects under the ceiling, so the upper bench is the hottest seat. A ceiling far above it wastes heat; one too low makes the top bench unbearable. That is why the bench height drives the ceiling height, which is 2,100 mm in many saunas and 2,500–2,750 mm in the ones Finnish builders prefer.
A sauna heater is chosen by room volume in cubic metres, not by floor area. Manufacturers publish a volume range for each heater. For example, an 18 kW heater suits 18–30 m³ and a 21 kW heater 24–36 m³.
A worked example: a room 3.0 m × 2.5 m with a 2.4 m ceiling is 18 m³. Give it a 4 m² glass front and the heater has to be sized for 18 + 4.8 = 22.8 m³. The room still looks like an 18 m³ sauna, but the heater has to be sized as if it were nearly 23 m³.
An undersized heater has to run longer and harder to reach temperature, and Harvia notes that this shortens its life. The heater also sets the electrical supply, so it has to be fixed before the electrical design, not after. A raised ceiling or a bigger glass front added late can mean a bigger heater and a new power supply.
A sauna needs fresh air. Without it, the air goes stale and guests leave early, even when the thermometer reads correctly.
This is what the brief for the engineers contains: room volume and surfaces, heater model and power, ventilation rates, controls and floor drainage. The full set of thermal-area figures is on our spa technical requirements page.
Guests use a sauna in cycles: heat, then cold, then rest, two or three times. The layout decides whether they complete those cycles.
The sauna is usually the cheapest heat experience to build. The hammam and steam room cost more, and how they compare is set out in our aquathermal journey design guide. To see how many saunas a whole spa needs, compare the three spa floor plan examples.
These are the numbers we check first when a commercial sauna is drawn. Each one has to be confirmed against the heater and sauna system finally selected.
| Element | Figure to plan around | Source |
|---|---|---|
| Seat width | About 60 cm of bench per seated person | Industry practice |
| Upper bench | 1,050–1,200 mm from the floor; 110–120 cm clear to the ceiling | Industry practice |
| Ceiling | 2,100 mm common; 2,500–2,750 mm preferred by Finnish builders | Industry practice |
| Heater | Chosen by volume, e.g. 18 kW for 18–30 m³, 21 kW for 24–36 m³ | Industry practice |
| Glass and stone | Each m² adds 1.2 m³ to the volume the heater is sized for | Harvia |
| Ventilation | Six air changes an hour; supply air above the heater with mechanical exhaust | Harvia |
| Temperature | 60–100 °C, low humidity | Vaisala |
| Heater safety | Sauna heaters are covered by IEC 60335-2-53 | IEC |
We plan the sauna as part of the whole spa: the bather numbers, the room size, the heater, the ventilation and electrical brief, and its place in the thermal circuit. We then specify the sauna and heater from manufacturers we work with.
The building work around the sauna (structure, waterproofing, drainage and the electrical supply) is done by your contractor to our brief. For the rest of the equipment, zone by zone, see our guide to professional spa equipment.
There is no single size. It is set by the number of bathers at the busiest hour: allow about 60 cm of bench per seated person, on two or three tiers, with the upper bench 1,050–1,200 mm above the floor. The room volume that follows from the benches then decides the heater.
The heater is chosen by room volume, not floor area, from the range the manufacturer publishes, for example 18 kW for 18–30 m³. Add 1.2 m³ for each square metre of glass or stone, as Harvia advises, and choose a heater rated for commercial use.
A Finnish-style sauna typically runs at 60–100 °C with low humidity. A steam room is very different: 40–50 °C at 100% humidity, with its own generator, drainage and sealed construction.
2,100 mm is common, and Finnish builders prefer 2,500–2,750 mm. What matters most is 110–120 cm of clearance above the upper bench: higher wastes heat, lower makes the top bench too hot.
Harvia recommends six air changes an hour. With mechanical exhaust, the supply air goes in above the heater so that incoming air is warmed straight away. The wet area around the sauna needs its own extract as well.